Check voltage drop for a given wire size or find the minimum AWG to stay within NEC-recommended limits. Single-phase and three-phase. Learn more
Check voltage drop for a given wire size or find the minimum AWG to stay within NEC-recommended limits. Single-phase and three-phase.
Your voltage drop will appear here, please add:
From quote to wire pull — Workiz keeps every job moving. Schedule, dispatch, invoice, get paid.
Voltage drop is the loss of voltage between the panel and the load as current travels through the wire's resistance. Too much drop means motors overheat, electronics misbehave, and runs waste energy as heat. The NEC recommends keeping drop at or below 3% on branch circuits and 5% total (branch + feeder combined).
Vd = 2·L·I·R / 1000 for single-phase and Vd = √3·L·I·R / 1000 for three-phase. Resistance values come from NEC Chapter 9 Table 8.Sizing a whole service before pulling wire? Use the electrical load calculator.